6. Informative Annexes
Annex A: Examples of Relay Settings
This informative annex provides examples of relay settings and input quantities to establish the operate/non-operate conditions during testing. The goal is to set the relay close to its operating threshold to maximize sensitivity to disturbances. Examples include:
- Independent time overcurrent relay: Energize with a current equal to the actual operate value minus a quantity corresponding to the claimed variation (e.g., -10% of set current).
- Instantaneous undervoltage relay: Energize with a voltage equal to the actual operating value plus a quantity corresponding to the claimed variation (e.g., +10% of set voltage).
- Under impedance relay: Energize with a current and voltage that results in an impedance equal to the actual operate value plus a quantity corresponding to the claimed variation (e.g., +15% of set impedance).
Annex B: Explanatory Notes on ESD
This annex provides context on the physics and practical aspects of electrostatic discharge.
- Source of ESD: The primary concern is discharge from the human body, especially in environments with dry atmosphere and synthetic fabrics. Charges are generated when an operator walks on a carpet or through friction with clothing.
- Discharge Behavior: The nature of the discharge depends on the path to earth. A good earth connection results in a very short duration, high amplitude current pulse (a few nanoseconds). A poor earth connection (high impedance) results in a damped oscillatory wave.
- Selection of Test Severity Classes: This annex provides environmental context for the severity classes.
| Class | Environment Description |
| Class 0 | Discharge voltage is kept negligible. |
| Class 1 | Discharge voltage is kept below 2 kV. For example, floors covered with antistatic material and relative humidity > 35%. |
| Class 2 | Discharge voltage is kept below 4 kV. For example, floors covered with antistatic material and relative humidity > 10%. |
| Class 3 | Discharge voltage is kept below 8 kV. For example, floors covered with synthetic material and relative humidity > 50%. This is normal for protection equipment. |
| Class 4 | Discharge voltage is kept below 15 kV. For example, floors covered with synthetic material and relative humidity > 10%. |